Packet Path/

Optics Reach Types Explained: SR, DR, FR, LR, ER and ZR

Every pluggable optic carries two letters that decide whether your link works at all: SR, DR, FR, LR, ER or ZR. Those letters are a reach class — the maximum distance the optic is built for — and each step up the ladder quietly changes the fibre, the connector and the price along with the distance. This article lays the whole ladder out as one table, explains what each step forces on you, and works one real pick end to end: a 300-metre campus link, and why the right answer there is DR or FR — not the LR pair people buy to be safe.

Data Center · Intermediate · 11 min · November 5, 2026

Editorial illustration on a dark teal background: a row of six pluggable optical modules labelled SR, DR, FR, LR, ER and ZR, each shining a beam of light a different distance toward buildings spaced further and further away.

The short answer

What do SR, DR, FR, LR, ER and ZR mean on an optic? They are reach classes — the longest link that optic is designed to carry. SR is the short one: 100 metres on multimode fibre. DR steps to 500 metres on single-mode. FR reaches 2 kilometres, LR 10 kilometres, ER 40 kilometres, and ZR is the coherent class built for spans of 80 kilometres and beyond. You choose the first class on that ladder that covers your actual distance — because every step up also changes the fibre and connector the link needs, and costs more. If you remember one sentence, make it that one: the letters are a ceiling you must clear, not a quality grade you should max out.

Think of it like shoe sizes for light. A link has a length, the way a foot has a length. An optic that is too small — an SR asked to cover 300 metres — simply does not fit, and no configuration command will stretch it. An optic several sizes too big technically fits, but you paid for leather you will never use, and in optics the oversize also shows up as a bigger power draw on every port, every hour, for the life of the switch. The craft is measuring the foot honestly, then buying the size that fits it.

In plain EnglishReach class: the two letters naming the maximum distance an optic type is built for. Multimode fibre (MMF): fibre with a wide core that carries light in many paths at once — cheap and forgiving over short runs, but the paths smear into each other over distance, which is why multimode classes stop at about 100 m. Single-mode fibre (SMF, OS2): a hair-thin core that carries one path of light — the only way to go kilometres. Lane: one optical channel; a 400G optic with four 100G lanes is a 4-lane optic. Parallel optics: each lane gets its own fibre pair, so the connector carries many fibres at once. WDM (wavelength-division multiplexing): the opposite trick — several lanes ride one fibre pair at different colours (wavelengths) and are separated at the far end. Coherent: a long-haul technique that encodes data in the light wave's phase as well as its brightness, surviving tens of kilometres and amplifier chains. MPO: a wide push-on connector that joins many fibres (12 or 16) in one plug. Duplex LC: the familiar two-fibre connector — one fibre each way.

The reach ladder, in one table

Here is the whole ladder at the speeds engineers buy today (the 100G and 400G generations — the classes and distances are the same idea at other speeds, with SR distances varying a little by speed and fibre grade). Read it left to right: as the distance grows, watch the fibre flip from multimode to single-mode at DR, and the connector flip from many-fibre MPO plugs to a single duplex pair at FR.

ClassMaximum reachFibre it needsConnector on the common formsWhere it lives
SR (short reach)100 m on OM4 multimode (70 m on OM3)Multimode, 850 nmMPO-12 (SR4) or MPO-16 (400G SR8)Inside one data hall — rack to rack, row to row
DR (datacenter reach)500 mSingle-mode, 1310 nmMPO-12 parallel (DR4); duplex LC on single-lambda DRAcross a large data centre, or building to building where single-mode is already in the ground
FR (fibre reach)2 kmSingle-mode, four CWDM wavelengths on one pairDuplex LCCampus links and short data-centre interconnects where fibre pairs are precious
LR (long reach)10 kmSingle-modeDuplex LCAcross a campus or a city — the classic metro edge link
ER (extended reach)40 kmSingle-modeDuplex LCMetro rings and provider backhaul
ZR (coherent DWDM class)80 km class and beyond — 400ZR runs roughly 40 km unamplified and up to about 120 km over an amplified line systemSingle-mode, one DWDM wavelengthDuplex LCData-centre interconnect between sites, on a DWDM line system
SR 100 m — multimode DR 500 m — single-mode FR 2 km — single-mode, one pair LR 10 km — single-mode ER 40 km — single-mode ZR 80 km class + Bars are stepped, not to scale: each class reaches roughly 2–5x further than the one above it.

Two patterns in that table do most of the work in real designs. First, the fibre flips once and never flips back: everything from DR upward is single-mode, so a building wired only with multimode has exactly one class available to it — SR — and a hard 100-metre ceiling. Second, the expensive steps are not the long ones, they are the boundary ones: the moment a link outgrows SR you are re-cabling or re-using single-mode, and the moment it outgrows DR you move from parallel fibre to wavelength multiplexing. Distance decides, but fibre and connectors are what you actually buy.

The number after the letters

The digit counts optical lanes: SR4, DR4, FR4 and LR4 each carry four lanes (at 400G, four lanes of 100G; at 100G, four of 25G). SR8 carries eight lanes of 50G. The lane count matters because it decides the connector and the breakout options. A DR4's four lanes travel on four separate fibre pairs through one MPO-12 plug — which is exactly why a DR4 can be broken out into four independent 100G links, one per pair. An FR4's four lanes are multiplexed onto a single duplex pair, which saves fibre but ends the breakout story: there are no separate pairs to split. Same letters-plus-number shape, very different cabling consequences — the companion piece on port breakout works through what one high-speed port can become.

And a rule with no exceptions worth gambling on: both ends of a link must be the same class and lane plan. A DR4 facing an FR4 looks plausible on a purchase order — both single-mode, both in the 1310 nm neighbourhood, both 400G — and will never link, because one is speaking on four fibre pairs and the other on four wavelengths down one pair. Match the full designation at both ends, the way you would match both ends of any other cable standard.

One pick, worked end to end: 300 metres across a campus

The job: a 400G link between two buildings 300 metres apart. Single-mode fibre is already buried between them — some as MPO trunks, and a couple of spare duplex pairs. Walk the ladder:

SR8 — out. Its ceiling is 100 m on OM4 multimode. The link is 300 m and the fibre in the ground is single-mode anyway. SR fails on distance and on fibre type at the same time; this is the undersize shoe.

DR4 — fits, with room. Rated to 500 m, so the 300 m link clears the ceiling with 200 m to spare. It wants the MPO-12 single-mode trunk, and as a bonus it can break out to four 100G DR links later if the port's job changes. If the MPO trunk is free, this is the natural buy.

FR4 — also fits, differently. Rated to 2 km over one duplex LC pair. It wastes reach on paper (2,000 m of ceiling for a 300 m link), but it spends only one fibre pair — if pairs are scarce and MPO trunks are spoken for, FR4 is the right answer for a cabling reason, not a distance reason.

LR4 — fits, and is the trap. Rated to 10 km, it will link perfectly. It will also cost more per module and draw more power on every port, forever, to buy 10,000 m of reach for a 300 m job — about 33 times the distance actually travelled. Nothing about that overspend makes the link more reliable: reach class is a ceiling, not a margin. The margin that protects a link from dirty connectors and repair splices lives in the optical power budget, which is a separate calculation with its own article and calculator on this site.

Verdict: DR4 if the parallel single-mode trunk is available (cheapest class that fits, breakout kept), FR4 if only a duplex pair can be spared. LR enters the conversation only when the route genuinely grows past 2 km.

Reach is a ceiling, not a promise

One honest limit before the mistakes list. A reach class says the optic is designed to work up to that distance on the specified fibre — it does not promise your particular link works. A 9 km LR link with too many patch panels and splices can still fail its power budget, because every connector spends light; that is what the link budget calculation is for, and it is worth running for any link you cannot easily revisit. At the ZR end the promise frays further: coherent reach is really a noise and dispersion budget, which is why 400ZR links are planned with an OSNR planner rather than a tape measure. The ladder tells you which shelf to shop on; the budgets tell you whether the specific link survives.

The mistakes that waste money

1. Buying LR for everything, to be safe. Safety does not live in the reach letters. An LR on a 300 m link adds cost and watts, not margin — margin is the spare decibels in the power budget.

2. Assuming single-mode optics interoperate. DR and FR are both single-mode and both live near 1310 nm, and they cannot talk to each other. Match the full class at both ends.

3. Forgetting the fibre you actually have. A hall wired in multimode caps you at SR and 100 m no matter what the switches support. The ladder is climbed on the fibre in the ground, not the fibre in the catalogue.

4. Reading SR's 100 m as universal. That figure is on OM4; on OM3 the same class is rated 70 m, and older multimode grades are shorter still. Check the grade before trusting the headline number.

5. Counting reach and skipping the budget. Distance is one line of the design. Connector and splice losses decide whether the light arrives — run the budget before the purchase order, not after the link flaps.

Fact-check sourcesThe reach figures are the standard class definitions used across IEEE 802.3 Ethernet interfaces and vendor datasheets for the 100G/400G generations: SR4/SR8 at 100 m on OM4 (70 m on OM3 for SR4), DR/DR4 at 500 m on single-mode, FR/FR4 at 2 km, LR/LR4 at 10 km, ER at 40 km, and ZR as the coherent DWDM class — with 400ZR's roughly 40 km unamplified and up-to-about-120 km amplified figures matching this site's own 400ZR article and planner presets. Connector facts (MPO-12 parallel fibre for DR4 with 4x breakout, duplex LC with CWDM wavelengths for FR4/LR4) follow the same datasheets. Exact figures vary by speed generation and vendor part — a production order verifies them against the datasheet of the actual module being bought.

Try it yourself

Reach class picks the optic; the budget proves the link. Take the worked 300 m pick and stress it in the free optical link budget calculator: choose a long-reach preset, set the distance first to 0.3 km and then to 9 km, and watch how the margin — not the distance — is what actually runs out as connectors and splices pile up. Then, if that 400G port might ever need to become four 100G links, check which optic forms allow it in the free 400G/800G port breakout planner — it is the DR forms, with their separate fibre pairs, that break out, and the FR and LR forms, multiplexed onto one pair, that do not.

Key takeaways